Integrated Fire & Gas Detection System (IFG)
System Description
AutroSafe IFG
Protecting life, environment and property...
116-P-ASAFE-IFG/XE Rev. B, 2005-10-27
Seitenansicht 0
1 2 3 4 5 6 ... 85 86

Inhaltsverzeichnis

Seite 1 - AutroSafe IFG

Integrated Fire & Gas Detection System (IFG) System Description AutroSafe IFG Protec

Seite 2

IFG Functionality System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and

Seite 3 - Table of Contents

IFG Functionality System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and

Seite 4

IFG Functionality 3.11 Local/External mode functionality Local/External functionality is selected via the AutroSafe configuration tool, as default, i

Seite 5

System Hardware 4. System Hardware 4.1 System Panels System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev.

Seite 6 - 1. Introduction

System Hardware System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 7 - 2. System Overview

System Hardware 4.2 AutroFieldBus Driver EAU-341 4.2.1 Description The AutroFieldBus driver EAU-341 is a communication protocol converter between the

Seite 8 - 2.2 System Example

System Hardware 4.2.3 Connections to EAU-341 All connections are made to plug-in screw terminals numbered 1-32. System Description, AutroSafe Integr

Seite 9 - 3. IFG Functionality

System Hardware Power and earth connections If a single earth systems is used both IE and PE must be connected to the earth. 12349101112AA’EAU-341BB

Seite 10 - IFG Functionality

System Hardware 4.2.5 Connection between EAU-321 and EAU-341 Communication Cable XBA-055 is used between the Serial Communication Board EAU-321 and A

Seite 11 - (from SW 3.5.0)

System Hardware 4.2.7 Jumper Settings for the EAU-321 board The table below gives an overview of the jumper settings for the Serial Port Communicatio

Seite 12 - 3.13 Language

COPYRIGHT © This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose. Autronica Fire and Security AS an

Seite 13 - 4. System Hardware

System Hardware 4.3 PowerLoop Driver BSD-340 4.3.1 Description The PowerLoop Driver BSD-340 functions as a protocol converter between AutroFieldBus a

Seite 14 - Main Function Description

System Hardware 4.3.3 Connections Note AutroFieldBus is not polarity-dependent. PowerLoop is polarity-dependent. BSD-34024V Out In126A+A- B+ B- AA&a

Seite 15 - 4.2.2 Overview

System Hardware System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 16 - System Hardware

System Hardware System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 17

System Hardware 4.4.4 Overview System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autro

Seite 18

System Hardware 4.4.6 Connection – current source 4.4.7 Connection – current sink System Description, AutroSafe Integrated Fire & Gas D

Seite 19

System Hardware 4.5 PowerLoop 4-20 mA Input Unit BN-342/EX 4.5.1 Description The PowerLoop 4-20mA Input Unit BN-342/EX is a general purpose PowerLoo

Seite 20 - 4.3.2 Overview

System Hardware 4.5.4 Connections BN-342/EX24V5+-++-+67812344-20mA input To detectorIn OutPowerLoop-- 4.5.5 Earthing If shielded cable is used on the

Seite 21 - 4.3.3 Connections

System Hardware 4.6 AutroFlame Multispectrum Flame Detector X33/1 PL 4.6.1 Description The AutroFlame Multispectrum Flame Detector X33/1 PL utilises

Seite 22

System Hardware 4.6.3 Connections X33/1PL + - + - 1 3 18 15 In OutPowerLoop Shielded cable is required for the PowerLoop, the shielding should be co

Seite 23 - 4.4.2 Versions

Table of Contents System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and

Seite 24 - 4.4.5 Connections

System Hardware 4.7 AutroPoint Gas Detector HC300 PL The AutroPoint HC300 PL is a diffusion-based, infrared combustible gas detector that provides co

Seite 25

System Hardware 4.7.1 Connections 2 1 3 AutroPoint HC300 PL Shielded cable is required for the PowerLoop, the shielding should be conti

Seite 26 - 4.5.3 Overview

System Hardware 4.8 AutroFieldBus Protocol Converter BSD-321 4.8.1 Description BSD-321 functions as a protocol converter between AutroFieldBus and va

Seite 27 - 4.5.5 Earthing

System Hardware System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 28 - 4.6.2 Applications

System Hardware 12349101112AA’BSD-321BB’*31 IEAFB earthfault sensorPrevious AFB unitNext AFB unit12349101112AA’BSD-321BB’*31IEAFB earthfault sensorPre

Seite 29 - 4.6.3 Connections

System Hardware 4.8.3.1 Power supply connections The BSD-321 is intended for use with 24VDC power supplies. It may be used in single or dual earth sy

Seite 30

System Hardware 4.8.3.3 RS-485 Detector interface 56781517181920272816AABBABrefBSD-321detector56781517181920272816AABBABrefBSD-321detectorABRS-485 ca

Seite 31 - 2 1

System Hardware System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 32 - 4.8.2 Overview

System Hardware 4.8.5 Typical applications using different signal references Application 1 The schematic drawing below shows an application where the

Seite 33 - 4.8.3 Connections

System Hardware Application 2 The schematic drawing below shows an application where the reference is coupled to the detector’s reference. The RS-485

Seite 34

Table of Contents System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and

Seite 35

System Hardware Application 3 The schematic drawing below shows an application where the detector has common signal reference and Earth. The shield an

Seite 36

System Hardware 4.8.6 Port Isolation on RS-422 ports The schematic drawings show the RS-422 ports on the BSD-321. Each port is isolated from the re

Seite 37 - 4.8.4 Earthing

Projecting Guidelines System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire

Seite 38

Projecting Guidelines System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire

Seite 39

Projecting Guidelines System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire

Seite 40

Projecting Guidelines System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire

Seite 41 - ,VRODWLRQ

Projecting Guidelines System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire

Seite 42 - 5. Projecting Guidelines

Projecting Guidelines System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire

Seite 43 - 5.2.2 Loop data

Projecting Guidelines 5.6.3 Single Earth Systems – Power Loop Firstly, consider a Single Earth system for simplicity. 1) All PowerLoop cabling must

Seite 44 - 5.2.3 Cable data

Projecting Guidelines 4) Shield must be continuous The PowerLoop cable will be split in two segments, separated by field equipment including junction

Seite 45 - 5.2.5 Power Supply data

Table of Contents System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and

Seite 46 - 5.5 Configuration

Projecting Guidelines 5) Maximum cable length The PowerLoop Calculator will define the maximum length of each cable segment, this tool however determ

Seite 47 - 5.6.2 Definitions

Projecting Guidelines 5.6.5 Shielding & Earthing AutroFieldBus Each unit that may be connected to AutroFieldBus has described the local earthing

Seite 48 - Max 30 cm

Projecting Guidelines System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire

Seite 49 - Note jumper !

PowerLoop Calculator Tool 6. PowerLoop Calculator Tool 6.1 Introduction The PowerLoop Calculator Tool is an integrated part of the AutroSafe Configura

Seite 50 - Projecting Guidelines

PowerLoop Calculator Tool 6.2 Operating The PowerLoop Calculator Tool 6.2.1 Loop driver type Select first the PowerLoopDriver type (BSD-340 or BSD-3

Seite 51

PowerLoop Calculator Tool The Power In, Power Out and Cable Loss are calculated. Power In: Power supplied to the BSD-340, i. e. the total power

Seite 52

PowerLoop Calculator Tool 6.2.5 Delete Row Button • Select a row in the list box above to delete a row, then press Delete Row Button. When pressing

Seite 53 - 6. PowerLoop Calculator Tool

PowerLoop Calculator Tool 6.2.8 Gra+phical Button This view shows only the loop units and the cable segments. If a (or several) Junction Box is includ

Seite 54 - 6.2.2 Add Button

PowerLoop Calculator Tool 6.2.9 Ambient Temperature A maximum ambient temperature of the BSD-340 Loop Driver must be entered. The ambient temperatu

Seite 55 - 6.2.4 Update Row Button

PowerLoop Calculator Tool System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica

Seite 56 - PowerLoop Calculator Tool

Introduction System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and Secu

Seite 57 - 6.2.8 Gra+phical Button

Operation 7. Operation 7.1 IFG-specific Menus The IFG-specific menus are included in the Show Status Menu (Inhibited Points) and Service Menu (Oil and

Seite 58 - 6.2.10 Save and Load File

Operation 7.2 Menu Structure – AutroSafe 3.5.0 - IFG Access Level > 2: Access by key.Access Level 3: Key and password restricted.Menu Structure –

Seite 59

Operation 7.3 Show Status Menu / Oil&Gas Inhibited Points Fire AlarmsFire WarningsFaultsShow StatusFire Alarm DevicesFire Alarm Routing Equipm

Seite 60 - 7. Operation

Operation 7.3.1 Show Status – Oil & Gas Inhibited Points This menu gives detailed information on Oil & Gas Inhibited points. The example bel

Seite 61 - Integrated Fire & Gas

Operation 7.4 Service Menu / Oil&Gas Commands Inhibit PointCancel Inhibit PointOil & Gas CommandsSet Alarm LimitsGet Measurement ValuesInhib

Seite 62 - Show Status

Operation System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and Securit

Seite 63 - SHOW STATUS

Operation 7.4.2 Cancel Inhibit Point The procedure describes how to cancel the inhibition of point(s). System Description, AutroSafe Integrated Fire

Seite 64 - Oil & Gas Commands

Operation System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and Securit

Seite 65 - Operation

Operation 7.4.3 Set Alarm Limits The Set Alarm Limits command allows you to change a gas detector’s alarm limit for Low Alarm and High Alarm. Syste

Seite 66 - 7.4.2 Cancel Inhibit Point

Operation System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and Securit

Seite 67

System Overview System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 68 - 7.4.3 Set Alarm Limits

Operation 7.4.4 Get Measurement Values System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-2

Seite 69

Operation System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and Securit

Seite 70

Operation 7.5 Show All Points In systems configured for IFG-functionality, the command Show all points is shown in the event of an alarm (Action Digi

Seite 71

Troubleshooting System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 72 - FIRE ALARMS

Troubleshooting System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 73 - 8. Troubleshooting

Troubleshooting System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 74 - AutroFieldBus faults:

Troubleshooting System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 75 - PowerLoop faults:

Troubleshooting System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 76 - Troubleshooting

Troubleshooting System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 77 - BN-342 faults:

Troubleshooting System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 78

System Overview 2.2 System Example The illustration below depicts a system consisting of panels networked on an AUTROLON network. For compliance with

Seite 79 - Dräger XPtox configuration:

Troubleshooting System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 80 - BSD-321 faults:

Troubleshooting System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and S

Seite 82

Reader’s Comments System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and

Seite 83 - 9. Reader’s Comments

Reader’s Comments System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and

Seite 84 - Reader’s Comments

Reader’s Comments System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and

Seite 85

Autronica Fire and Security AS is an international company, based in Trondheim, Norway and has a world-wide sales and service network. For more th

Seite 86

IFG Functionality System Description, AutroSafe Integrated Fire & Gas Detection System, 116-P-ASAFE-IFG/XE Rev. B, 2005-10-27, Autronica Fire and